S700 Safety: Several S700 on One Safety Control | 19 Dec 2011 | |

S700 Safety: Several S700 on One Safety Control

Valid for S700

Question

Is it possible to connect a safe output to the safe inputs (STO) of several servo amplifiers?

Validity

The information below applies to the following products:

Servo amplifier

Manufacturer Product designation HWR
Kollmorgen S701...S772 2.1

Safety controllers

Manufacturer Product designation Product version
Pilz PNOZ m0p base unit
PNOZ m1p base unit
PNOZ m2p base unit
PNOZ m3p base unit
PNOZ mo1p expansion module
All

Several switch-off paths can be operated in parallel on the safe 1-pole HL output of the aforementioned safety controllers. This is valid for up to 9 drives.  

Safety analysis

A safety analysis has been carried out with regard to the switch-off paths and their controller. The effect of a random error in a switch-off path on the switch-off behavior of the whole arrangement has been investigated.

ATTENTION:
The user must ensure that a "Stuck-at-One" error cannot occur within the electrical installation in accordance with EN ISO 13849-2:2003, table D.5. A short circuit against the supply voltage would mean that none of the servo amplifiers in the parallel connection could be switched off.

Response times

Parallel connection has no effect on the specified response times.

Achievable safety level

Can Sil2 still be achieved? Does this change the characteristic data?
SIL2/PLd is achievable for the safety function STO with switch-off paths connected in parallel. The safety characteristic data in the current operating instructions is still valid.

Can Sil3 still be achieved?
Due to the specified test sequence for SIL3/PLe (independent tests on both switch-off paths for each servo amplifier), this safety level cannot be achieved with a parallel connection.

Back to top