Function Operation Mode ISO  13849-1 IEC 61508-2 PFH [1/h] TM [Years] SFF [%]
STO single channel PL d, CAT 2 SIL 2 1.88E-07 20 89
STO dual channel PL d, CAT 3 SIL 2 5.64E-09 20 87
STO dual channel with periodical testing PL d, CAT 4 SIL 3 5.64E-09 20 87